The frequency converter is a power control device that converts the power frequency power source into another frequency by using the on/off function of the power semiconductor device. With the rapid development of modern power electronics technology and microelectronic technology, high-voltage and high-power variable frequency speed control devices have been continuously matured, and the high voltage problem that has been difficult to solve has been solved in recent years by device series or unit series.
1. The difference between voltage source type and current source type high voltage inverter
The main circuit of the inverter can be roughly divided into two categories: voltage source type and current source type. The voltage source type is a frequency converter that converts the direct current of the voltage source into an alternating current, and the filter element of the direct current loop is a capacitor; the current source type is an inverter that converts the direct current of the current source into an alternating current, and the direct current loop filter component is an inductor.
2. Why does the output voltage of the inverter change in proportion to the frequency?
The torque of the asynchronous motor is generated by the interaction between the magnetic flux of the motor and the current flowing in the rotor. At the rated frequency, if the voltage is constant and only the frequency is reduced, the magnetic flux is too large, the magnetic circuit is saturated, and the motor The current increases and the motor will burn out if it is severe. Therefore, the frequency and voltage should be changed in proportion, that is, the frequency of the inverter is controlled while changing the frequency, so that the magnetic flux of the motor is kept constant to avoid the occurrence of magnetic saturation. This is the definition of VVVF. The voltage here refers to the effective value of the line voltage or phase voltage of the motor.
3. When the motor is driven by the commercial frequency power supply, the current increases when the voltage drops; for the inverter drive, if the voltage drops when the frequency decreases, then if the current increases the frequency (low speed), if the same power is output, the current increases. However, under a certain torque condition, the current is almost constant.
4. What is the starting current and starting torque of the motor when the inverter is running?
The inverter is operated, and the frequency and voltage are increased correspondingly with the acceleration of the motor. The starting current is limited to 150% of the rated current (125% to 200% depending on the model). When starting directly with a commercial power supply, the starting current is 6 to 7 times, so a mechanical and electrical impact will occur. It can be started smoothly with the inverter drive (starting time becomes longer). The starting current is 1.2 to 1.5 times of the rated current, and the starting torque is 70% to 120% of the rated torque. For the inverter with the torque automatic enhancement function, the starting torque is 100% or more, and it can be started with full load.
5. What does V/f mode mean?
The voltage V also decreases proportionally as the frequency decreases. This problem has been explained in answer 4. Maintaining the V/f ratio constant control is the most basic control method for asynchronous motor frequency conversion speed regulation. It controls the voltage output of the inverter while controlling the change of the power frequency of the motor, and makes the ratio V/f constant. Keep the magnetic flux of the motor constant. Under the rated operation of the motor, the voltage drop of the stator resistance and leakage reactance of the motor is relatively small, and the terminal voltage of the motor and the induced potential of the motor are approximately equal.
The main problem with V/f ratio constant control is poor low speed performance. The reason is that the proportion of the stator resistance voltage drop of the asynchronous motor becomes large at low speed, which can not be ignored. It can no longer be considered that the stator voltage and the motor induced potential are approximately equal, and the motor flux can not be kept constant according to the V/f ratio control. The reduction of the motor flux will inevitably reduce the electromagnetic torque of the motor; in addition, the dead time of the inverter power device is also an important reason that affects the low-speed performance of the motor. The dead time causes the voltage to drop and also causes the torque ripple. Under the conditions, it will also cause the oscillation of the speed and current.
V/f ratio constant control is commonly used on general purpose inverters. This kind of frequency converter is mainly used for the speed control function of fans and pumps, and the occasions where the speed regulation range is not high. The outstanding advantage of the V/f ratio constant control is that the open loop speed control of the motor can be performed.
6. How does the torque of the motor change when V and f are changed proportionally?
When the frequency is lowered to completely reduce the voltage proportionally, since the AC impedance becomes small and the resistance does not change, the torque generated at the low speed tends to decrease.
Therefore, given V/f at low frequencies, the output voltage must be increased to obtain a certain starting torque. This compensation is called enhanced starting. It can be implemented in various ways, such as an automatic method, selecting a V/f mode, or adjusting a potentiometer.
7. What does it mean to open the ring?
The speed sensor is installed on the motor used, and the actual speed is fed back to the control device for control. It is called “closed loopâ€. If the speed sensor is not used, it is called “open loopâ€. The general inverter is mostly open loop.
8, high-voltage inverter's own protection function
Output overload, output overcurrent, grid overvoltage, grid undervoltage, grid power loss, DC bus overvoltage, DC bus undervoltage, transformer overheat, phase loss, control power failure, drive fault, power device overheating, cooling fan failure , external given drop, ground fault, fiber fault, etc.
Small computer system interface (SCSI) is an independent processor standard for system level interfaces between computers and intelligent devices (hard disks, floppy drives, optical drives, printers, scanners, etc.). SCSI is an intelligent universal interface standard.
1. SCSI can support multiple devices, SCSI-2 (fastscsi) can connect up to 7 SCSI devices, and widescsi-2 can connect 15 SCSI devices. In other words, all devices only need to occupy one IRQ. At the same time, SCSI also supports a wide range of devices, such as CD-ROM, DVD, CDR, hard disk, tape drive, scanner, etc.
2. SCSI also allows one device to transfer data and another device to look up its data. This can achieve higher performance in multitasking operating systems such as Linux and windows NT.
3. SCSI occupies a very low CPU, so it has obvious advantages in multitask system. Since the SCSI card itself has a CPU, it can handle all the transactions of SCSI devices. When the host CPU sends work instructions to the SCSI card, the SCSI card will work by itself. After the work is finished, the work results will be returned to the CPU. In the whole process, the CPU can carry out its own work.
4. The SCSI device is also intelligent. The SCSI card can queue CPU instructions by itself, which improves the work efficiency. In multitasking, the hard disk will be in the current head position, and the adjacent tasks will be completed first and then processed one by one.
5. The fastest SCSI bus has a bandwidth of 160MB / s, which requires the use of a 64 bit 66MHz PCI slot. Therefore, the maximum speed that can be achieved in the PCI-X bus standard is 80mb / s. if it is used with a dedicated hard disk with 10000rpm or 15000rpm, it will bring obvious performance improvement.
SCSI-180°DIP Section
ShenZhen Antenk Electronics Co,Ltd , https://www.antenk.com